A Circuit Breaker 600 Ampere 48 Voltage Normal Open Double Coils Dc Cotactor For Communication Power Industry
1. Summary
JQ-600H(B)/48-48BW DC contactor has a set of bridge normally opened contactors with load current up to 600A. Accord with GB1408.4-2010/IEC60947-4-1:2009 Ed.3.0.MOD, YD/T585-2010. Suitable for communication power equipment electrical control device.
2. Usage condition
Ambient temperature: work | - 40 ~ + 60; storage and transportation: - 40 ~ + 70 |
relative humidity | 98% at 40 |
altitude | not more than 2000 meters |
Vibration | 10-55hz |
amplitude | 0.35mm |
impact | 30m/s2 |
3. Standard,safty and environmental protection
(1) Comply with GB14048.4-2003 / IEC60947-4-1:2000 low voltage switching equipment and control equipment electromechanical contactor and motor starter standard.
(2) YD/T585-2010 General credit distribution equipment technical conditions.
4. Specification
Parameter | Coil voltage of contact circuit |
Voltage range | 6-220v |
Coil power | 5-8w |
Normal state | Normally opened |
Main rated load current of contact circuit | 600A |
Rated voltage of contact circuit | 6-80v |
Sucking time | 40ms |
Releasing time | 30ms |
Mechanical life | 100000times |
Electric life | 1000times |
Coil resistance | 603.6-708.4Ω |
4. Order mark standard
5. Current actual production parameter
No. | requirements | unit | 24 | 48 | 60 | |
1 | Coil resistance under 20℃ | Ω | 144.5 | 578 | 909 | |
Coil consuming resistance | W | 4 | 4 | 4 | ||
Coil resistance error | Ω | ±8% | ±8% | ±8% | ||
2 | Action features | |||||
Cold suction voltage:45~75%Ue | V | 9.6~16.8 | 19.2~33.6 | 24-42 | ||
Cold release voltage10%Ue~40%Ue | V | 2.4~9.6 | 4.8~19.2 | 6-24 | ||
Contact pressure drop of main contact | mv | ≤60 |
6. Current curve
6. The circuit diagram of the configuration, installation and terminal
7. The schematic diagram of the terminal circuit
8. Products
9. Application of low voltage DC contactor