JQ - 200H 200 Ampere Series 24,48,54,62 Voltage Double Coil Single Pole Normal Open For Dc Voltage
1. DC contactor Summary
JQ-200H(B)/48-48BW DC contactor has a set of bridge normally opened contactors with load current up to 200A. Accord with GB1408.4-2010/IEC60947-4-1:2009 Ed.3.0.MOD, YD/T585-2010. Suitable for communication power equipment electrical control device.
2. Usage condition
Ambient temperature: work | - 40 ~ + 60; storage and transportation: - 40 ~ + 70 |
relative humidity | 95% at 40 |
altitude | not more than 2000 meters |
Vibration | 10-55hz |
amplitude | 0.35mm |
impact | 30m/s2 |
3. Standard,safty and environmental protection
(1) Comply with GB14048.4-2003 / IEC60947-4-1:2000 low voltage switching equipment and control equipment electromechanical contactor and motor starter standard;
(2) YD/T585-2010 General credit distribution equipment technical conditions.
4. Parameter table
Parameter | Coil voltage of contact circuit |
Voltage range | 6-220v |
Coil power | 5-8w |
Normal state | Normally opened |
Main rated load current of contact circuit | 200A |
Rated voltage of contact circuit | 6-80v |
Sucking time | 40ms |
Releasing time | 30ms |
Mechanical life | 100000times |
Electric life | 1000times |
Coil resistance | 603.6-708.4Ω |
5. Order mark standard
JQ - 200H(B)/48 - 48BW
JQ | DC Ccontactor |
200 | Rated load 200A |
H | Normally Opened |
(B) | Communication power |
B | Double coil |
48 | The contact voltage |
48 | The contact voltage |
W | Bending mounting plate |
6. Current curve
7. The circuit diagram of the configuration, installation and terminal
8. Series of products presentation